ZF10-145G(L)/T3150-40 Gas Insulated Switchgear
Service and Installation Conditions
Installation site: Indoor/outdoor
Ambient temperature: -15℃~+40℃(indoor)/-30℃~+40℃(outdoor)
Altitude: 1000m (No limitation for special order)
Humidity:
Relative humidity at average per day (25℃): ≤95%
Relative humidity at average per month: ≤90%
Wind speed: ≤35m/s (wind pressure ≤700Pa)
Sunshine intensity: 0.1w/cm (at wind velocity of 0.5m/s)
Icing thickness: 10mm
Seismic intensity:
Horizontal acceleration: ≤0.4g
Vertical acceleration:≤0.2g
Symmetrical Creepage distance: 25mm/kV (pollution class III), 31mm/kV (class IV)
Keep the breaker away from places with combustible, explosive, corrosive materials and violent vibrations.