  • 集合式高压并联电容器.jpg

Integrated HV Shunt Capacitor


HV shunt capacitor is shunt connected with AC power electric system PF (50Hz or 60Hz) equals and above 1kV, which is used to improve the power factor and voltage quality, reduce line loss, and implement the efficiency of power generation and supply.
CONTACT

Working Condition
Installation site: Indoor/outdoor
Altitude: ≤1000m (No restrictions for special order)
Ambient air temperature: Minimum temperature is -25℃ and -40℃. Maximum parameters are identified into A, B, C and D, namely 40℃, 45℃, 50℃, and 55℃.
Seismic degree: The capacitor could withstand seismic degree of 8, without any demage.
The ambient environment should be without obvious pollution, such as corrosive or flammable gas or steem, and etc.
When the capacitor put into commissioning, residual voltage on the terminal should be less than ten persents of rated voltage.
3 Main Parameters
Rated frequency: 50Hz
Capacitance deviation: -5%~+15%
Tangent of loss angle tgδ(Under rated voltage and 20℃): ≤0.0005 (excluding internal fuse)
Long-term operation under 1.05 times of rated voltage could be admissable, for 1.15 times could be within 30min per 24hrs.
For capacitor wih maximum positive deviation capacitance, steady state over-current could be 1.5In.

COMPANY INFO
1Name:Shandong Taikai Power Engineering Co.,Ltd
1Address: Taikai Industrial Park, High-tech Zone, Taian city, Shandong Province
1Tel:86-538-8625668
1Web:www.tk-electric.com
CONTACT INFO

1
Wechat

1
Mobile Website

Copyright © 2022 ALL Shandong Taikai Power Engineering Co., Ltd. SEO 300.cn 鲁ICP备15016584号-2