Shandong Taikai Power Engineering Co., Ltd. is here to serve you wholeheartedly!
Integrated HV Shunt Capacitor
Working Condition
Installation site: Indoor/outdoor
Altitude: ≤1000m (No restrictions for special order)
Ambient air temperature: Minimum temperature is -25℃ and -40℃. Maximum parameters are identified into A, B, C and D, namely 40℃, 45℃, 50℃, and 55℃.
Seismic degree: The capacitor could withstand seismic degree of 8, without any demage.
The ambient environment should be without obvious pollution, such as corrosive or flammable gas or steem, and etc.
When the capacitor put into commissioning, residual voltage on the terminal should be less than ten persents of rated voltage.
3 Main Parameters
Rated frequency: 50Hz
Capacitance deviation: -5%~+15%
Tangent of loss angle tgδ(Under rated voltage and 20℃): ≤0.0005 (excluding internal fuse)
Long-term operation under 1.05 times of rated voltage could be admissable, for 1.15 times could be within 30min per 24hrs.
For capacitor wih maximum positive deviation capacitance, steady state over-current could be 1.5In.
Address: Taikai Industrial Park, High-tech Zone, Taian city, Shandong Province
Tel:86-538-8625668
Web:www.tk-electric.com